PMA TB 40-1

Image
  • Applicable for heating and cooling applications
  • For all types of thermocouples and resistance transducers
  • BluePort Front interface and BlueControl Software
  • Maintenance manager and error list
  • Alarm reset via RESET-key
  • Alarm reset via digital
Image

The TB40-1 limit controller has been type tested to DIN standards. 

The TB40-1 can be used for heating and refrigeration processes. It is suitable for all thermocouple types and resistance type sensors. It is particularly designed for use in: 

  • All applications where an over or under temperature fault condition could present fire hazard or other hazard
  • Heating system in buildings to DIN EN 12828
  • Large hot-water boilers to DIN EN 12953-6
  • Thermal transfer plants with organic heat transfer media to DIN 4754
  • Oil-fired installations to DIN 4755

 

Benefits & Features 

  • Applicable for heating and cooling applications
  • For all types of thermocouples and resistance transducers
  • BluePort Front interface and BlueControl Software
  • Maintenance manager and error list
  • Alarm reset via RESET-key
  • Alarm reset via digital
  • Type tested to EN 14597 and cULus

 

Specification 

Product Category: Limit Controller
Dimensions and size: 96mm x 48mm x 118mm (HxWxD), 1/8 DIN
Connectors: Pins or screw terminals
Primary Input Type: Universal (TC, RTD, DC linear mA/mV)
Output Type: Relay
Max. Number of Outputs: 3
Control Type: Temperature limiter
Power Supply:

100–240V AC 50–60Hz

20-48V AC 50/60 Hz

22-65V DC

Panel Sealing: IP65 
Certifications: CE, Type tested to EN 14597 (replaces DIN 3440), cULus
Software Tools: BlueControl

 

As a result of updates to EN 14597(2009-1) the original TB 40-1 device can no longer be used as a temperature limiter, but only as a temperature monitor. Enhanced versions of the TB 40-1 are now available which can be used either as limiters (TB) or monitors (TW).

 

From January 2012 onwards, models with part number TB40-1x0-xxxxx / TB40-1x1-xxxxx are considered as temperature monitors.
The new models with part numbers TB40-1x2-xxxxx / TB40-1x3-xxxxx can be used either as limiters (TB) or monitors (TW).